Incoflex XLPE NCLAD - Pre-clad Foil Facer

Incoflex XLPE N-CLAD – A high-performance, pre-clad insulation that provides built-in weather resistance, eliminating the need for additional on-site jacketing or coatings. Pre-cladded – Provides extra mechanical protection against impacts. Superior Fire Reaction – Meets strict fire safety standards for all applications. Moisture & Vapor Barrier – Prevents condensation and corrosion in HVAC. Weather & UV Resistance – Suitable for exposed applications, including outdoor and high-humidity environments. No Additional Jacketing Required – Comes with a factory-applied protective layer, eliminating the need for extra on-site coatings or weatherproofing. Versatile Industrial Use – Ideal for HVAC, cooling districts, buried systems , underground tunnels, oil & gas, and heavy industries.

Technical Data Table
Technical Specifications
PROPERTY VALUE / RESULT STANDARD TEST METHOD
Density 1.5 to 2.5 lb/ft³ (25 to 40 Kg/m³) ASTM C1427
Service Temperature (foam only) from -58°F to 230°F (−50°C to 120°C) ASTM C177
Thermal Conductivity at mean temperature BTU·in/h·ft²·°F (W/mK) 50°F (10°C): 0.22 (0.032) ASTM C518 / ASTM C177
75°F (23°C): 0.23 (0.033)
95°F (35°C): 0.24 (0.036)
113°F (45°C): 0.26 (0.038)
Water Vapour Transmission ≤ 7.29x10⁻⁹ g/Pa·s·m ASTM E96
Water Vapour Permeance ≤ 0.63 x 10⁻¹² g/Pa·s·m² ASTM E96
Water Vapour Permeability 0.05 perm-inch ASTM E96
Vapour Diffusion Resistance Factor (μ) > 80,000 BS EN 12086
Water Absorption (Liquid phase) < 0.1% (by volume) ASTM C209
Resistance To Fungi No Growth ASTM G21
Resistance To Bacteria No Growth ASTM G22
CFC & HCFC Free Comply USEPA 8260 B
VOC Level (Green Star Rating) Low VOC Emitting ASTM D5116
Surface Burning Characteristics Class A (FSI<25 and SDI<50) ASTM E84
Surface Spread of Flame Class 0 BS 476 part 6 and 7
Classification of Reaction to Fire B-s1,d0 EN 13501-1
Fire Test on Building Materials 0, 0, 0, 1 AS/NZS 1530.3
Fire Hazard Properties Group 2 ISO 5660 / AS 5637.1 & AS NZS 3837
VOC Emissions TVOC’s ≤ 0.5 mg/m²/h CDPH V1.2, LEED V1.4, GREENGUARD
Formaldehyde: ≤ 0.05 ppm Individual
VOCs: ≤ 0.05 ppm for specific VOCs

Cross-linked closed-cell polyolefin thermal insulation foam

Incoflex XLPE is a high performance cross-linked polyolefin thermal insulation material designed for superior energy efficiency and durability. It complies with ASTM C1427, ensuring high-quality standards for closed-cell thermal insulation. This versatile insulation solution is widely used in building and construction, HVAC, refrigeration, plumbing, oil / gas and other industrial applications, providing excellent thermal resistance, moisture resistance, and long-term performance

Reducing CO₂ Emissions Through Superior Thermal Efficiency

Reduces CO₂ Emissions – By improving thermal efficiency and reducing energy demand, Incoflex XLPE helps cut carbon dioxide (CO₂) emissions, supporting global efforts toward environmental sustainability

Health, Environment, and Indoor Air Quality Benefits of Incoflex XLPE

Incoflex XLPE has a minimized volatile organic compound (VOC) emission, contributing to better indoor air quality and a healthier environment. Unlike some insulation materials, Incoflex XLPE does not release harmful fibers or particles into the air, reducing respiratory risks. Its closed-cell structure prevents moisture buildup, which helps inhibit the growth of mold, mildew, and bacteria, improving hygiene and air quality. Produced with environmentally responsible processes, reducing waste and promoting sustainability. Helps lower energy consumption in HVAC, refrigeration, and plumbing systems, reducing carbon footprints and supporting green building initiatives. Free from CFCs, HCFCs, and other ozone-depleting substances, making it a safe choice

Features

XLPE Catalog (2025)

Enquiry Form